Thermic Valves and Check Valves | LK 821 ThermoVar Technical Data 36 Registered Design LK 821 ThermoVar LK 821 ThermoVar 3-way thermic zone valve is designed to change the direction of flow of the media in heating systems. The valve is controlled by the temperature of the media. With an LK 821 ThermoVar installed in, for example, a solar heating system an optimal stratification in the storage tank is obtained. LK 821 can be equipped with an insulation - see under Accessories. For more information, please see the product sheet for insulations page 49. The valve can be mounted at any angle. LK 821 ThermoVar can easily be adapted for right- or left-hand mounting. Opening temperature 45°C, 55°C, 61°C, 66°C, 72°C or 80°C Working temperature 45°C - 55°C Min. +5°C/Max. +95°C 61°C - 80°C Min. +5°C/Max. +110°C Ambient temp. Min. +5°C/Max. +60°C Max. working pressure 1.0 MPa (10 bar) Max. differential pressure 50 kPa Media Water - Glycol mixture max. 50% Thread standard Rp - female thread, G - male thread Material, valve body Brass EN 12165 CW617N Material, cover Brass EN 12165 CW617N Material, sealing EPDM Capacity Diagram Kvs (m³/h) 12 10.0 9.0 6.0 4.0 (m ³/h) 1.0 Flow 0.1 0.1 1.0 10.0 100.0 Pressure drop (kPa)